101,On tank fire (detection) alarm system (1) - Doer equipment

Classification:Industry PublishTime:2019-11-05 14:44:01

About tank fire (detection) alarm system


For the tank fire detection and alarm system, according to the code for construction and acceptance of automatic fire alarm system (GB 50166-92), relevant product instructions and system diagrams and site conditions, the connection between the dry powder fire extinguishing system equipment and the alarm system should be correctly connected.


Alarm control settings:


One flameproof three wavelength infrared flame detector with 4-20mA output and standby switch signal is set around the vent pipe;


Vent pipe: 1 platinum thermistor, explosion proof instrument control terminal box at tank bottom, module, switch signal output (120h, 65L signal dual output);


Three flame-proof combustible gas detectors are set at the positions where the emptying pipeline on the top of the tank is easy to leak; 4-20mA output, standby switch signal;


The tank top is equipped with two platinum thermistors (Platinum thermistors are symmetrically arranged), the explosion-proof instrument control terminal box at the bottom of the tank is equipped with modules, and the switch signal output (65L signal dual output).